This website uses cookies and similar technologies (“cookies”). Subject to your consent, will use analytical cookies to track which content interests you, and marketing cookies to display interest-based advertising. We use third-party providers for these measures, who may also use the data for their own purposes. 

You give your consent by clicking "Accept all" or by applying your individual settings. Your data may then also be processed in third countries outside the EU, such as the US, which do not have a corresponding level of data protection and where, in particular, access by local authorities may not be effectively prevented. You can revoke your consent with immediate effect at any time. If you click on "Reject all", only strictly necessary cookies will be used.
You are here: Home » Products » Connector » Separable Connector » Environmental Protection Cabinet Emergency Power Fast Socket

loading

Environmental Protection Cabinet Emergency Power Fast Socket

Model: 12kV 
Rated current: up to 200A
Material: Silicone Rubber&Epoxy resin
Application: emergency power supply
Bushing model: EN50180 & 50181 interface A
Execution Standards: IEC60502.4, GB/T12706.4
Availability:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
sharethis sharing button
  • NKS-YJKC12/200-02

  • NKS POWER

Environmental Protection Cabinet Emergency Power Fast Socket product introduction:


NKS POWER emergency power quick socket is used for 10kV primary and secondary integrated ring main unit-voltage transformer interval, 10kV ring main unit-voltage transformer cabinet. In order to meet the requirements of 10kV uninterrupted power operation and power extraction, an environmentally friendly gas is added The insulated ring main unit power outage operation interface PT cabinet solution is structurally integrated with the node switching power supply in the original PT cabinet. The difference from the emergency quick socket of SF6 gas insulated cabinet is that the epoxy sleeve adds an umbrella skirt to increase the creepage distance. The other usage methods are the same.


Product execution standards: IEC60502.4, GB/T12706.4, GB/T11022

This product matches Type A bushings in EN50180&50181.


Emergency Power Fast Socket product features:


Used for emergency and rapid power extraction of environmentally friendly gas cabinets

The insulated plug is molded from safe and environmentally friendly silicone rubber

Reasonable epoxy bushing structural design increases creepage distance

The opening size is recommended to comply with the 202 casing standard, with a diameter of 73.5mm.

Quick assembly and simple installation


Electrical performance parameters of Emergency Power Fast Socket:


NKS-YJKC12/200-02

Items

Parameter

Technical Parameters System Voltage

12kV

Rated current

200A

Frequency withstand voltage(AC)

45kV/1min

Partial Discharge

15kV<10pC

Impulse voltage

95kV

Temperature rise test Temperature rise at connector contact ≤50K

Temperature rise of terminals on both sides ≤65K


The product has passed the inspection and certification of the China Electric Power Research Institute (CEPRI) Power Industry Electrical Equipment Quality Inspection and Testing Center

Type test reference standard: IEC 60502-4:2010 GB/T 12706.4-2008

17001877254251700187654467


Previous: 
Next: 
The company adheres to the concept of environmental friendliness and smart connection, and is willing to work with you to create green and sustainable development, leading smart technology power industry.

Product Category

Quick Links

Contact Us
Address:  No. 11, 6th Industrial Zone, Mashantou Community, Ma Tian Street, Guangming District, Shenzhen, CN 
Tel:  +86-755-2666-0819 
Mobile&Wechat&WhatsApp: +86-135-1015-8968 
Copyright © 2023 Shenzhen NKS Power Technology Co., Ltd. All Rights Reserved. Support by leadongSitemap. Privacy Policy
Leave a Message
Contact Us